Table A.1:
MV cable types. Type 12 (sub-transmission cable) and types 6-11 (legacy cables) are not used for new cable installations in MV DNEP.
ID Type Inom R(Ω/km) X(Ω/km) C(μF/km) Cost (€/km
120 mm2 215 A 0.257 0.085 0.38 50 000 
150 mm2 295 A 0.20858 0.09592 0.3833 59 000 
240 mm2 370 A 0.13517 0.10823 0.43553 62 000 
400 mm2 475 A 0.08077 0.09972 0.5344 66 000 
630 mm2 605 A 0.0511 0.09272 0.64103 73 000 
N/A 135 A 0.53253 0.09777 0.27072 N/A 
N/A 160 A 0.3737 0.09367 0.30671 N/A 
N/A 195 A 0.26756 0.08995 0.34505 N/A 
N/A 225 A 0.32829 0.10134 0.32667 N/A 
10 N/A 320 A 0.13079 0.07757 0.53109 N/A 
11 N/A 350 A 0.10193 0.08004 0.48485 N/A 
12 N/A N/A N/A N/A N/A N/A 
ID Type Inom R(Ω/km) X(Ω/km) C(μF/km) Cost (€/km
120 mm2 215 A 0.257 0.085 0.38 50 000 
150 mm2 295 A 0.20858 0.09592 0.3833 59 000 
240 mm2 370 A 0.13517 0.10823 0.43553 62 000 
400 mm2 475 A 0.08077 0.09972 0.5344 66 000 
630 mm2 605 A 0.0511 0.09272 0.64103 73 000 
N/A 135 A 0.53253 0.09777 0.27072 N/A 
N/A 160 A 0.3737 0.09367 0.30671 N/A 
N/A 195 A 0.26756 0.08995 0.34505 N/A 
N/A 225 A 0.32829 0.10134 0.32667 N/A 
10 N/A 320 A 0.13079 0.07757 0.53109 N/A 
11 N/A 350 A 0.10193 0.08004 0.48485 N/A 
12 N/A N/A N/A N/A N/A N/A 